NMC-PRO Installation Manual
83Page
ALARM MENU
Delta EC Pre-Control High: If the measured EC Pre-Control value is higher than the target value plus Delta
EC Pre-Control High, the system will generate a High EC Pre-Control Alarm.
Emergency EC High (1 minute delay): If the measured EC is higher than the value set here for more than 1
minute, the system will be stopped. This setting should be used to protect the plants/system and should
generally be higher than the EC High Alarm based on the dosing-program target value plus the Delta EC
High.
Emergency pH Low (1 minute delay): If the measured pH is lower than the value set here for more than 1
minute, the system will be stopped. This setting should be used to protect the plants/system and should
generally be lower than the pH Low Alarm based on the dosing-program target value minus the Delta pH Low.
7.6 EC/pH Alarm Setting
The EC/pH alarm setting table allows you to define the desired response for EC/pH related failures recognized by the
NMC-Pro:
STOP: Stop irrigation and/or dosing for current valve (or valve group) and continue to the next valve (or valve
group).
CONT: Continue irrigation and/or dosing for the valve (or valve group) that caused the alarm. This option
actually means that the system will generate an alarm but will not take action.
Delay (mm:ss): Define the period the failure must be active before the NMC-Pro will generate an alarm and
will take action.
Alarm Active: Define whether the alarm output should be triggered by the appropriate alarm.
7.7 Radio Sys. Alarm Definition
IMPORTANT: For Radio System to work properly, MUST define in the 6.2 SYSTEM SETUP menu Remote
Unit type parameter SN/RF Net.
In this screen, define Radio Systems alarm activity and notification.
ACTIVE: Defines if alarm is used in making decisions regarding irrigation program (YES / NO)
INFORM: Defines if the system will notify the user of the alarm occurrence (YES / NO)
RADIO SYS. ALARM DEFINITION
Alarm Type
Delay
mm:ss
Active
Inform
RTU
Vbatt failure
Vbatt low
Vbatt warn
Cap failure
Card failure
I/O Open
I/O Shor
HOST
Over current
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
YES
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES