12.4 INPUT TYPE: (DC CURRENT)
ENTER INPUT TYPE MENU:
Press ‘MENU 1) Display shows "INPUt" Input Menu.
Press ‘RESET/ENTER 2)
Display flashes "VOLt" (default) or previous stored input type.
Press ‘/MAX 3) Scroll through the available following input type selection list. Display
flashes:
"VOLt" (DC Voltage)
"CURRNt" (DC Current)
"bRIdGE" (Bridge)
"POt" (Potentiometer)
"tC" (Thermocouple)
"Rtd" (RTD)
If the displayed input type is "CURRNt", press ‘RESET/ENTER to skip to
Step 6 (CURRNt" stops flashing).
CURRNt "CURRNt" CURRENT SUBMENU:
Press ‘/MAX 4) Scroll through the available selection to "CURRNt" (flashing).
Press ‘RESET/ENTER 5) Display shows "CURRNt" again, but not flashing.
Press ‘RESET/ENTER 6) Display flashes "0-20MA" current range (default) or previously stored
selection of current input range (see Table below for available current
ranges). If the display matches your choice of current range. Go to Step 8.
Press ‘/MAX 7) Scroll through the 2 available current input ranges to the selection of
your choice.
Press ‘RESET/ENTER 8) Display shows "StOREd" stored message momentarily and then
advances to the "RdG.CNF" Reading Configuration Menu.
CURRENT RANGES: 0 – 20 milliampere 4 – 20 milliampere
DISPLAY: 0-20MA
4-20MA
47
Input Type Selection