EasyManuals Logo

Omega DP41-B User Manual

Omega DP41-B
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
12.4 INPUT TYPE: (DC CURRENT)
ENTER INPUT TYPE MENU:
Press ‘MENU 1) Display shows "INPUt" Input Menu.
Press ‘RESET/ENTER 2)
Display flashes "VOLt" (default) or previous stored input type.
Press ‘/MAX 3) Scroll through the available following input type selection list. Display
flashes:
"VOLt" (DC Voltage)
"CURRNt" (DC Current)
"bRIdGE" (Bridge)
"POt" (Potentiometer)
"tC" (Thermocouple)
"Rtd" (RTD)
If the displayed input type is "CURRNt", press ‘RESET/ENTER to skip to
Step 6 (CURRNt" stops flashing).
CURRNt "CURRNt" CURRENT SUBMENU:
Press ‘/MAX 4) Scroll through the available selection to "CURRNt" (flashing).
Press ‘RESET/ENTER 5) Display shows "CURRNt" again, but not flashing.
Press ‘RESET/ENTER 6) Display flashes "0-20MA" current range (default) or previously stored
selection of current input range (see Table below for available current
ranges). If the display matches your choice of current range. Go to Step 8.
Press ‘/MAX 7) Scroll through the 2 available current input ranges to the selection of
your choice.
Press ‘RESET/ENTER 8) Display shows "StOREd" stored message momentarily and then
advances to the "RdG.CNF" Reading Configuration Menu.
CURRENT RANGES: 0 – 20 milliampere 4 – 20 milliampere
DISPLAY: 0-20MA
4-20MA
47
Input Type Selection
12

Table of Contents

Other manuals for Omega DP41-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omega DP41-B and is the answer not in the manual?

Omega DP41-B Specifications

General IconGeneral
BrandOmega
ModelDP41-B
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals