EasyManua.ls Logo

Omega DP41-B - Field Calibration for Cold Junction Compensation

Omega DP41-B
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
61
Input Configuration Menu
16
In case of "tC" input type:
Press ‘RESET/ENTER 10) Display shows "tC.CO.JC" Cold-Junction Compensation for "tC"
Thermocouple input type.
Press ‘RESET/ENTER 11) Display flashes
"ENAbLE" as default
or previous selection.
Press ‘/MAX 12)
To select either "ENAbLE" or "dISAbL" for your choice of setup.
Press ‘RESET/ENTER 13) Display shows "C.JUN.OF" Cold-Junction Offset Adjustment menu.
Press ‘RESET/ENTER 14) Display flashes "dISAbL" as default.
16.3.1 FIELD CALIBRATION FOR COLD JUNCTION COMPENSATION BOARD
CAL 0 Enter " CAL 0 " FIELD CALIBRATION SUBMENU:
*
The meter has been calibrated with the cold-junction compensation
board included with your unit. However if you change the board or
want to verify the calibration, this controller has technologically
featured with " CAL 0 " menu function for Field Calibration to
performCold-Junction Offset Adjustment automatically as described
in the following steps.
* Caution: Before attempting to calibrate, make sure you have the
proper equipment for calibration and follow the procedure precisely.
* The communication Bus Format, "bUS.FMt", must
be in
Command Mode, "COMMNd".
* RTD and Process are perfectly calibrated; this calibration is only
applicable to TC.
Equipment required
: Select proper TC type that you
need to calibrate and set your calibrator for 0°C / 32°F. Having
applied power, let the setup warm-up, for at least one hour, prior to
performing Field Calibration.
Press ‘/MAX 15) Select "ENAbLE" to enter FIELD CALIBRATION mode for
Cold-Junction Offset Adjustment.
Press ‘RESET/ENTER 16) Display advances to "CAL 0" Field Calibration submenu for
Cold-Junction Offset Adjustment.
*The following Step 17 is a safety measure to prevent unintentional
calibration.
Press ‘/MAX 17) Display still shows "CAL 0" Submenu.
Press ‘RESET/ENTER 18) Display shows "StOREd" stored message (meaning the calibration is
complete) momentarily and advances to "IN.SC.OF" Input Scale & Offset
configuration Submenu.

Table of Contents

Other manuals for Omega DP41-B

Related product manuals