Setpoint Configuration Menu
22
22. SETPOINT CONFIGURATION MENU: (SP.CNF)
Setpoints 1 through 4 can be configured for a very large variety of zone and level signaling.
SP1 and SP2 have balanced configurable hysteresis and are non-latching, suitable for control-level
signaling.
SP3 and SP4 are often used as Alarm1 and Alarm2, because they have single-sided hysteresis and
can be configured for latching action.
The levels of these Setpoints are entered during run mode via the front-panel pushbuttons (refer to
Setpoint Settings Menu Configuration Sections 8) and many performance options are selected during
the configuration mode in the following sections.
SP.CNF ENTER SETPOINT CONFIGURATION MENU:
Press ‘MENU 1) Six times, display shows "SP.CNF" Setpoint Configuration Menu.
Press ‘RESET/ENTER 2) Display flashes "dISAbL" (default) or previous selection.
Press ‘/MAX 3) Select "ENAbLE" to configure Setpoint 1 and Setpoint 2.