Setpoint Configuration Menu
76
SP1.CNF
Press ‘RESET/ENTER’ 4) Display shows "StOREd" stored message momentarily and then
advances to "SP 1.CNF" Setpoint 1 configuration submenu. If necessary,
press ‘MENU’ to select the other available following submenu: "SP
2.CNF" Setpoint 2 Configuration and "SP db" Setpoint Deadband
Configuration
Submenu. See Steps 12 through 16 for details.
Press ‘RESET/ENTER’ 5)
Display shows "ACt IVE" Setpoint Active State menu.
Press ‘RESET/ENTER’ 6)
Display flashes "AbOVE" Above Setpoint active state option or previous
setting.
Press ‘䊱/MAX’ 7) Scroll to select 2 available choices: "AbOVE" or "bELOU" (below)
Setpoint Active State.
Press ‘RESET/ENTER’ 8) Display shows "StOREd" stored message momentarily and then
advances to "N.StAtE" Normal State (Open-collector or Relay Output
active state) menu.
Press ‘RESET/ENTER’ 9) Display flashes "N.OPEN" Normal Open (Output collector or Relay
opened) state or previous setting "N.CLOSE" Normal Close (Output
Relay closed) state.
Press ‘䊱/MAX’ 10) Select your choice of Output Relay state setting.
Press ‘RESET/ENTER’ 11) Display shows "StOREd" stored message momentarily and then
advances to "SP 2.CNF" Setpoint 2 Configuration Menu.
SP2.CNF
Press ‘RESET/ENTER’ 12) "SP 2.CNF" Setpoint 2 Configuration submenu items are
& ‘䊱/MAX’ identical to "SP 1.CNF", proceed with your choices of setting then display
advances to "SP db" Setpoint Deadband Menu.
Press ‘RESET/ENTER’ 13)
Display shows "StOREd" stored message momentarily and then
advances to "SP db" Setpoint Deadband Configuration Submenu. Setpoint
Deadband is used to select the amount of hysteresis for the setpoints
programmable from "0000" to "9999").
SP db
Press ‘RESET/ENTER’ 14) Display shows some 4-digit number (0020 as default) of previous
setting with the first digit flashing.
Press ‘䊱/MAX’ & ‘
䊳
/MIN’ 15) To modify the value of Setpoint Deadband.
Press ‘RESET/ENTER’ 16) Display shows "StOREd" stored message momentarily and then
advances to "AL CNF" Alarm Configuration Menu.