Alarm Configuration Menu
24.3. AL db Enter ALARM DEADBAND MENU:
This selected deadband (hysteresis) for Alarm 1 ("SP3") and Alarm 2 ("SP4") is placed on the INACTIVE
side of the selected levels. This results in immediate action (if zero (0) delay is selected in "NUM.dLy")
When an alarm limit is exceeded, but defers recovery when the input returns to pre-alarm levels.
Press ‘MENU’ 19) Display shows "AL db" Alarm Deadband setup menu.
Press ‘RESET/ENTER’ 20)
Display shows some 4-digit number (0020 as default) of previous
settings with the first digit flashing.
Press ‘䊱/MAX’ & ‘
䊳
/MIN’ 21) To modify the value of Alarm Deadband for your desired setting.
Press ‘RESET/ENTER’ 22) Display shows "StOREd" stored message momentarily and then
advances to "NUM.dLy" Number of input readings required triggering
Alarm 1 (SP3) and Alarm 2 (SP4) action.
24.4. NUM.dLy Enter NUMBER OF READINGS/DISPLAY MENU:
Press ‘RESET/ENTER’ 23) Display shows two 2-digit numbers (03 03 as default) with the second
right side of display) one flashing.
Press ‘䊱/MAX’ 24) To modify the delay value or number of input readings before Alarm 2
response.
Press ‘
䊳
/MIN’ 25) To select Alarm 1‘s delay value setting, display flashing the first 2-digit
number (left side of the display). Pressing ‘MIN’ button allow users to
select Alarm 1 or Alarm 2‘s delay values.
Press ‘䊱/MAX’ 26) To modify the delay value or number of input readings before Alarm 1
response.
Press ‘RESET/ENTER’ 27) Display shows "StOREd" stored message momentarily and then
advances to "RSt AL" Alarm Reset submenu.
24.5. RSt AL Enter ALARM RESET CONTROL MENU:
Press ‘RESET/ENTER’ 28) Display flashes "dISAbL" (disable) or previous setting.
Press ‘䊱/MAX’ 29)
To enable "ENAbLE" or disable "dISAbL" both Alarm 1 and Alarm 2
(Setpoints 3 and 4) action and LEDs.
Press ‘RESET/ENTER’ 30) Display shows "StOREd" stored message momentarily and then
advances to "COMM" Communication parameter setting menu.