EasyManuals Logo

Omega DP41-B User Manual

Omega DP41-B
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
18
Multi-Point Scale and Offset Menu Configuration
68
Determine the correct values for Inputs ("INPUt 0" and
"INPUt 1"). Calculate "INPUt 0" and "INPUt 1"
using the following equation:
"INPUt" = (Sensor Output) x (Conversion Number)
Conversion number is a coefficient of conversion between input values and real full display
range (100000 counts). See table below for proper conversion number.
INPUT RANGE CONVERSION NUMBER
0 – 100 mV 100000/(100 x 1)=1000cts/mV
0 - 1 V 100000/(1000 x 1)= 100cts/V
0 - 10 V 100000/(1000 x 10)= 10cts/V
0 – 20 mA 20000/ (20 x 1) = 1000cts/mA
Table 18-1. Conversion Number Table
Determine "INPUt 0" and "INPUt 1" Input range. For our transducer select 0 – 100 mV range.
"INPUt 0" = 0 (mV) x 1000(cts/mV) = 000000
"INPUt 1" = 30 (mV) x 1000(cts/mV) = 030000
1. Determine correct values for Display Reading ("REAd 0" and "REAd 1")
2. In most cases,"REAd 0" and "REAd 1" are equal to the minimum and the maximum of the
transducer output range.
"REAd 0" = 000000
"REAd 1" = 000100
3. Scaling the controller.
Press ‘RESET/ENTER 18)
Display stops flashing "MANUAL" Manual Scaling method menu.
Press ‘RESET/ENTER 19) Display shows "StOREd" momentarily and advances to "INPUt 0"
heading.
Press ‘RESET/ENTER 20) Display shows last stored "INPUt 0" value with 1st digit flashing.
Press ‘/MAX & ‘
/MIN 21) To enter "INPUt 0" value (000000)
Press ‘RESET/ENTER 22) Display advances to "REAd 0" heading.
Press ‘RESET/ENTER 23) Display shows last stored "REAd 0" value with 1st digit flashing.
Press ‘/MAX & ‘
/MIN 24) To enter "REAd 0" value (000000).
Press ‘RESET/ENTER 25) Display shows "INPUt 1" heading.
Press ‘RESET/ENTER 26) Display shows last stored "INPUt 1" value with 1st digit flashing.
Press ‘/MAX & ‘
/MIN 27) To enter "INPUt 1" value (030000).
Press ‘RESET/ENTER 28) Display advances to "REAd 1" heading.
Press ‘RESET/ENTER 29) Display shows last stored "REAd 1" value with 1st digit flashing.
Press ‘/MAX & ‘
/MIN 30) To enter "REAd 0" value (000100).
Press ‘RESET/ENTER 31) Display shows "StOREd" momentarily and advances to "OUt.CNF"
Output Configuration Menu.

Table of Contents

Other manuals for Omega DP41-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omega DP41-B and is the answer not in the manual?

Omega DP41-B Specifications

General IconGeneral
BrandOmega
ModelDP41-B
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals