Inverter Positioning Section 5-3
Refer to
7-3 Analog Output Units
for operating procedures for the Analog Out-
put Unit.
Calculation Example
Conditions
Inverter’s maximum output frequency: 60 Hz
Calculation
The stored analog output value is calculated as follows:
Stored analog
output value
Inverter frequency
command value (Hz)
Inverter's max. output frequency (Hz)
6,000
CP1L
Automatic
calculations
Inverter
frequency
command value
Auxiliary Area
A23/A33
6,000
Inverter maximum
output frequency (Hz)
Stored analog
output value
Analog output
Unit: 0.01 Hz
1
100
Converting values in A23/A33 to Hz.
Converted in ladder program
Stored analog
output value
60
6,000
1
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
100
1