448
Analog I/O Units Section 7-4
7-4-2 CP1W-MAD11/CPM1A-MAD11 Analog I/O Units
Each CP1W-MAD11/CPM1A-MAD11 Analog I/O Unit provides 2 analog
inputs and 1 analog output.
• The analog input range can be set to 0 to 5 VDC, 1 to 5 VDC, 0 to
10 VDC, −10 to 10 VDC, 0 to 20 mA, or 4 to 20 mA. The inputs have a
resolution of 1/6000.
An open-circuit detection function can be used with the 1 to 5 VDC and 4
to 20 mA settings.
• The analog output range can be set to 1 to 5 VDC, 0 to 10 VDC, −10 to
10 VDC, 0 to 20 mA, or 4 to 20 mA. The outputs have a resolution of
1/6000.
Part Names
(1) Analog I/O Terminals
Connected to analog I/O devices.
Note For current inputs, short V IN0 to I IN0 and V IN1 to I IN1.
NC
NC
CP1W-MAD11/CPM1A-MAD11
(3) Expansion connecto