21
System Configuration Section 1-2
1-2-3 Restrictions on System Configuration
The following restrictions apply to the CP-series Expansion Units and CP-
series Expansion I/O Units that can be connected to CP1L CPU Units.
Number of Expansion Units and Expansion I/O Units Connected
A maximum of three Units can be connected to a CPU Unit with 30, 40 or 60
I/O points and one Unit can be connected to a CPU Unit with 20 or 14 I/O
points.
Mounting Restriction
When connecting CP-series or CPM1A-series Expansion Units or Expansion
I/O Units to a CPU Unit with AC power, provide a space of approximately 10
mm between the CPU Unit and the first Expansion Unit or Expansion I/O Unit.
If sufficient space cannot be provided between the CPU Unit and the first
Expansion Unit or Expansion I/O Unit, use the PLC in an ambient temperature
of 0 to 50°C.
Restrictions in the External Power Supply Capacity
The following restrictions apply when using the external power supply from a
CPU Unit with AC power.
CPU Units with 30, 40 or 60 I/O Points and AC Power (CP1L-M
@@DR-A
and CP1L-M@@DT@-A)
When CP1W or CPM1A Expansion Units or Expansion I/O Units are con-
nected to a CPU Unit with 30, 40 or 60 I/O Points and AC Power (CP1L-
M@@DR-A and CP1L-M@@DT-A), it may not be possible to use the entire 300
mA from the external power supply due to restrictions in the power supply
capacity. The entire 300 mA from the external power supply can be used if
Expansion Units and Expansion I/O Units are not connected.
Calculation Examples of Restrictions in External Power Supply Capacity
Calculate the external power supply capacity using the following calculation
example.
10 mm
CP1L CPU Unit
Expansion I/O Units or Expansion Units
Item CPU Unit Expansion Unit Total Restriction
1st Unit 2nd Unit 3rd Unit
CP1L-M40DR-A CP1W-DA041 CP1W-DA041 CP1W-DA041
5 V 0.22 A 0.08 A 0.08 A 0.08 A 0.46 A
24 V 0.08 A 0.124 A 0.124 A 0.124 A 0.452 A
Power con-
sumption
5 V × 0.46 A = 2.3 W
24 V × 0.452 A = 10.848 W
13.148 W 18.5 W
Applicable
external power
supply capacity
18.5 W (total external power supply capacity) 13.148 W = 5.352 W
5.352 W/24V = 0.223 A
0.223 A 0.3 A
Note If the results exceeds 0.3 A, reduce the current consumption to 0.3 A or less.