Pulse Outputs Section 5-2
Pulse Output with Trapezoidal Acceleration/Deceleration (Using PLS2(887))
5-2-8 Instructions Used for Pulse Outputs
The pulse output functions can be used by executing the pulse control instruc-
tions in the ladder program. For some instructions, the PLC Setup must be set
in advance. The following instructions can be combined for positioning and
speed control.
Supported Pulse
Instructions
Use the following 8 instructions to control the pulse outputs.
Determine the pulse output
method, output frequency, and port.
Wire the outputs.
PLC Setup settings
Enable/disable the origin search function. Set the
various origin search parameters if the origin
search function is enabled.
Ladder program
PLS2(887): Specify port number and set the
output method (CW/CCW method or Pulse +
direction method) and pulse output control with
trapezoidal acceleration/deceleration (different
rates can be set for acceleration and
deceleration).
INI(880): Specify port number and stop pulse
output when necessary.
PRV(881): Specify port number and read pulse
output PV when necessary.
Pulse output method
CW/CCW inputs
Pulse + direction inputs
Output frequency: 1 Hz to 100 kHz (1 Hz units)
J models: 1Hz to 20 kHz (1 Hz units)