242
Pulse Outputs Section 5-2
The following table shows the kinds of pulse outputs controlled by each
instruction.
Instruction Function Positioning (independent mode) Speed control
(continuous mode)
Origin
search
Pulse
output
without
accelera-
tion/
decelera-
tion
Pulse output with accel-
eration/deceleration
Pulse
output
without
accelera-
tion/
decelera-
tion
Pulse
output
with
accelera-
tion/
decelera-
tion
Trapezoi-
dal, equal
accelera-
tion/ decel-
eration
rates
Trapezoi-
dal, sepa-
rate
accelera-
tion/ decel-
eration
rates
PULS(886)
SET PULSES
Sets the number of pulses
to be output.
Used --- --- --- --- ---
SPED(885)
SPEED OUTPUT
Performs pulse output con-
trol without acceleration or
deceleration.
(When positioning, the
number of pulses must be
set in advance with
PULS(886).)
Used --- --- Used --- ---
ACC(888)
ACCELERATION
CONTROL
Performs pulse output con-
trol with acceleration and
deceleration.
(When positioning, the
number of pulses must be
set in advance with
PULS(886).)
--- Used --- --- Used ---
PLS2(887)
PULSE OUTPUT
Performs pulse output con-
trol with independent
acceleration and decelera-
tion rates.
(Also sets the number of
pulses.)
--- --- Used --- --- ---
ORG(889)
ORIGIN SEARCH
Actually moves the motor
with pulse outputs and
determines the machine
origin based on the Origin
Proximity Input and Origin
Input signals
--- --- --- --- --- Used
INI(880)
MODE CONTROL
Stops the pulse output.
Changes the pulse output
PV. (This operation deter-
mines the origin location.)
Used Used Used Used Used ---
PRV(881)
HIGH-SPEED
COUNTER PV
READ
Reads the pulse output PV. Used Used Used Used Used ---
PWM(891)
PULSE WITH
VARIABLE DUTY
FACTOR
Performs pulse output con-
trol with variable duty fac-
tor pulse output.
--- --- --- --- --- ---

Table of Contents