EasyManua.ls Logo

Omron CP1L - 5-3-12 Application Example with an Analog Output

Omron CP1L
763 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
327
Inverter Positioning Section 5-3
Internal Work Addresses
Settings Addresses
Modbus Communications
Add the above instructions to the end of the program as a starting condition
for the ladder programming example. For error processing, refer to the ladder
program in
6-3-3 Modbus-RTU Easy Master Function
and to the inverter’s
manual.
5-3-12 Application Example with an Analog Output
Positioning with
Trapezoidal Control
Specifications and
Operation
When start input CIO 1.04 turns ON, 600,000 pulses are output internally for
inverter positioning 0 to turn the motor shaft.
Note Refer to
5-3-7 Determining the Internal Pulse Output Frequency
for the for-
mula to convert the frequency and use the converted internal pulse frequency.
The number of output pulses is calculated from the encoder specifications
and the high-speed counter multiplier.
Address Usage
D1 Bits 00 to 03: Run/Stop Command
D2 Bits 00 to 15: Frequency Command Value
D10 Bits 00 to 03: Forward/Reverse Command
D15 Bit 09: Forward/Reverse Command
Address Usage Data
D32200 Bits 00 to 07: Slave address 01
D32201 Bits 00 to 07: Function code 10
D32202 Bits 00 to 07: Number of communications data bytes 09
D32203 Bits 00 to 15: Register number of write start data 0001
D32204 Bits 00 to 15: Number of data registers to write 0002
D32205 Bits 08 to 15: Number of attached data bytes 04
D32206 Bits 00 to 07: Upper bytes of frequency command value in D2
Bit 08: Run/Stop Command
Bit 09: Forward/Reverse Command
---
D32207 Bits 08 to 15: Lower bytes of frequency command value in D2 ---
A26.00
Operation
Command Flag
A641.00
Modbus-RTU Master Execution Bit

Table of Contents

Other manuals for Omron CP1L

Related product manuals