713
PLC Setup Appendix G
Pulse Output 1 Settings
Base Settings
Name Default Settings When setting is read 
by CPU Unit
Internal 
address
Bits Settings
1 Undefined Origin (oper-
ation for limit signal turn-
ing ON)
Hold Hold At start of operation 286 12 to 
15
0 hex
Undefined 1 hex
2 Limited Input Signal 
Operation
Search Only Search Only When power is turned 
ON
274 04 to 
07
0 hex
Always 1 hex
3 Limit Input Signal NC NC At start of operation 286 00 to 
03
0 hex
NO 1 hex
4 Search/Return Initial 
Speed
0 pps 
(disabled)
0 pps At start of operation 277 and 
276
00 to 
15
0000 0001 
hex
 :  :
100,000 pps 0001 86A0 
hex
000F 4240 
hex
5 Speed Curve Trapezium Trapezium When power is turned 
ON
274 12 to 
15
0 hex
S-shaped 1 hex