356
Interrupt Functions Section 6-1
CPU Units with 14 I/O Points
CPU Units with 10 I/O Points
Input terminal block Default setting High-speed counter settings
Word Bit Single-phase
(increment pulse
input)
Two-phase
(differential phase x4,
up/down, or
pulse/direction)
Origin searches
CIO 0 00 Normal input 0 High-speed counter 0:
Increment input
High-speed counter 0:
Phase A, Increment, or
Count input
---
01 Normal input 1 High-speed counter 1:
Increment input
High-speed counter 0:
Phase B, Decrement,
or Direction input
---
02 Normal input 2 High-speed counter 2:
Increment input
High-speed counter 1:
Phase A, Increment, or
Count input
Pulse output 0: Origin
proximity input signal
03 Normal input 3 High-speed counter 3:
Increment input
High-speed counter 1:
Phase B, Decrement,
or Direction input
Pulse output 1: Origin
proximity input signal
04 Normal input 4 High-speed counter 0:
Phase Z or reset input
High-speed counter 0:
Phase Z or reset input
---
05 Normal input 5 High-speed counter 1:
Phase Z or reset input
High-speed counter 1:
Phase Z or reset input
---
06 Normal input 6 High-speed counter 2:
Phase Z or reset input
--- Pulse output 0: Origin
input signal
07 Normal input 7 High-speed counter 3:
Phase Z or reset input
--- Pulse output 1: Origin
input signal
Address Default setting High-speed counter Operation settings:
Word Bit Single-phase
(increment pulse
input)
Two-phase
(differential phase x4,
up/down, or
pulse/direction)
Origin searches
CIO 0 00 Normal input 0 Counter 0, increment
input
Counter 0, A phase, up,
or count input
---
01 Normal input 1 Counter 1, increment
input
Counter 0, B phase,
down, or direction input
---
02 Normal input 2 Counter 2, increment
input
Counter 1, A phase, up,
or count input
---
03 Normal input 3 Counter 3, increment
input
Counter 1, B phase,
down, or direction input
Pulse output 0: Origin
proximity input signal
04 Normal input 4 Counter 0, phase-Z
reset input
Counter 0, phase-Z
reset input
---
05 Normal input 5 Counter 1, phase-Z
reset input
Counter 1, phase-Z
reset input
Pulse output 0: Origin
input signal

Table of Contents