401
Memory Cassette Functions Section 6-6
All valid data in the Memory Card will be automatically transferred to the CPU
Unit.
Note When this function is executed, at least the user program must be stored on
the Memory Cassette.
This function can be used to copy data to another CPU Unit without using the
CX-Programmer.
User programs can be overwritten to upgrade equipment versions without
using the CX-Programmer.
If writing data from the CPU Unit to the Memory Cassette and the CPU Unit is
set to use the operating mode specified in the PLC Setup as the operating
mode after automatic transfer at startup, operation can be started without
cycling the power, enabling operation from the Memory Cassette.
Programs, parameters, DM initial values,
comment memory, etc. (Can be specified
individually.)
CP1L CPU Unit
Data in CPU
Unit
Power turned ON.
DIP switch SW2 set to ON.
Data automatically transferred from Memory
Cassette to CPU Unit.
Programs, parameters, DM initial
values, comment memory, etc.
CP1L CPU Unit
Data in CPU
Unit
CP1W-ME05M
Memory Cassette
Another CPU Unit
Can be automatically
transferred at startup.