435
Analog Output Units Section 7-3
Connect the Analog Output Unit to the CPU Unit.
Internal Circuits
■ Wiring for Analog Outputs
Note (1) Connect the shield to the FG terminal to prevent noise.
(2) Separate wiring from power lines (AC power supply lines, high-voltage
lines, etc.)
(3) When there is noise in the power supply line, install a noise filter on the
input section and the power supply.
(4) When external power is supplied (when range codes are set), or when the
power is interrupted, there may be a pulse status analog output of up to
1 ms. If this status is a problem, take the following measures.
• Turn ON the power to the CP1L CPU Unit, check the operation status,
and then turn ON the power at the load.
• Turn OFF the power to the load and then turn OFF the power to the
CP1L CPU Unit.
1. Connecting the Analog Output Unit
CH
I OUT1 I OUT3
I OUT2
VOUT1
VOUT2
VOUT3
COM1
COM2
I OUT4
VOUT4
COM4
NC
AG
COM3
OUT
SYSMAC
CP1L
L1 L2/N
COM010305070911010305070911
00 02 04 06 08 10 00 02 04 06 08
10
00 01 02 03 04 06 00 01 03 04 06
COM COM COM COM 05 07 COM 02 COM 05
07
IN
OUT
CPU Unit
CP1W-DA041
CPM1A-DA041
Analog Output Unit
2. Wiring Analog Outputs
Analog output 1
Analog ground
NC
I OUT1
COM1 (−)
V OUT1
I OUT4
COM4 (−
)
V OUT4
Analog output