697
PLC Setup Appendix G
Timings: Time and Interrupt Settings
Cycle Time Settings
Interrupt Setting
Name Default Settings When setting is read
by CPU Unit
Internal
address
Bits Settings
1 Watch Cycle Time
(default 1000 ms)
Use default. Use default.
(Default: 1 s)
At start of operation 209 15 0
Use user setting. 1
1-1 Watch Cycle
Time (default
1000 ms)
1,000 ms 1: 1 × 10 ms At start of operation 209 00 to
14
001 hex
: :
40,000:
40,000 × 10 ms
FA0 hex
2Cycle Time
(No Setting)
No minimum
cycle time
No minimum cycle time At start of operation 208 00 to
15
0000 hex
1 ms 0001 hex
: :
32,000 ms 7D00 hex
Name Default Settings When setting is read
by CPU Unit
Internal
address
Bits Settings
1 Scheduled Interrupt
Interval
10 ms 10 ms At start of operation 195 00 to
03
0 hex
1 ms 1 hex
0.1 ms 2 hex