EasyManuals Logo

Omron MX2 Series User Manual

Omron MX2 Series
612 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #171 background imageLoading...
Page #171 background image
4 Parameter List
4 - 11
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
PID Braking
A077
PID Deviation
Reverse Output
00: Disabled (Deviation = Target value
Feedback value)
01: Enabled (Deviation = Feedback
value Target value)
00
Enabled
P. 7-44
A078
PID Variable Range
Limit
0.0 to 100.0
0.0
Enabled
%
A079
PID Feedforward
Selection
00: Disabled
01: O (Voltage)
02: OI (Current)
00
Enabled
AVR
A081
1st AVR Selection
00: Always ON
01: Always OFF
02: OFF during deceleration
02
Enabled
P. 7-42
A281
2nd AVR Selection
02
Enabled
A082
1st Motor Rated Volt-
age Selection
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
200/400
Disabled
V
P. 5-20
A282
2nd Motor Rated
Voltage Selection
200/400
Disabled
V
A083
AVR
Filter Time
Constant
0.000 to 10.000
0.300
Enabled
s
P. 7-42
A084
AVR Gain at Deceler-
ation
50. to 200.
100.
Enabled
%
Operation
mode,
acceleration/deceleration
function
A085
Operation Mode
Selection
00: Normal operation
01: Energy-saving operation
00
Disabled
P. 7-50
A086
Energy-saving
Response/Accuracy
Adjustment
0.0 to 100.0
50.0
Enabled
%
A092
1st Acceleration
Time 2
0.00 to 3600.00
*1
10.00
(15.00)
*2
Enabled
s
P. 5-36
A292
2nd Acceleration
Time 2
10.00
(15.00)
*2
Enabled
A093
1st Deceleration
Time 2
10.00
(15.00)
*2
Enabled
A293
2nd Deceleration
Time 2
10.00
(15.00)
*2
Enabled
A094
1st
2-step Acceleration/
Deceleration Selection
00: Switch via 2CH terminal (multi-func-
tion input: 09)
01: Switch by setting (A095/A295/
A096/A296)
02: Switch only during forward/reverse
switching
00
Disabled
A294
2nd
2-step Acceleration/
Deceleration Selection
00
Disabled
A095
1st
2-step Acceleration
Frequency
0.00 to 590.00
0.00
Enabled
Hz
A295
2nd
2-step Acceleration
Frequency
0.00
Enabled
A096
1st
2-step Deceleration
Frequency
0.00
Enabled
A296
2nd
2-step Deceleration
Frequency
0.00
Enabled
A097
Acceleration
Pattern Selection
00: Line
01: S-shape curve
02: U-shape curve
03: Inverted U-shape curve
04: EL-S-shape curve
01
Disabled
P. 5-33
A098
Deceleration
Pattern Selection
01
Disabled
4
4-3 Extended Function Mode
4-3-1 Group A: Standard Function Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC

Related product manuals