Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Overload
limit, overcurrent
protection
1st Overload Limit
Selection
00: Disabled
01: Enabled during acceleration and
constant speed
02: Enabled during constant speed
03: Enabled during acceleration and
constant speed (Accelerated during
regeneration)
2nd Overload Limit
Selection
0.20 Rated current to 2.00 Rated cur-
rent (Heavy load)
0.20 Rated current to 1.50 Rated cur-
rent (Light load)
Rated
current
1.50
(Normal)
1.20
(Light)
1st Overload Limit
Parameter
2nd Overload Limit
Parameter
1st Overload Limit
Selection 2
00: Disabled
01: Enabled during acceleration and
constant speed
02: Enabled during constant speed
03: Enabled during acceleration and
constant speed (Accelerated during
regeneration)
1st Overload Limit
Level 2
0.20 Rated current to 2.00 Rated cur-
rent (Heavy load)
0.20 Rated current to 1.50 Rated cur-
rent (Light load)
Rated
current
1.50
(Normal)
1.20
(Light)
1st Overload Limit
Parameter 2
Overcurrent Suppres-
sion Selection
00: Disabled
01: Enabled
02: Enabled (at reduced voltage
startup)
Frequency Pull-in
Restart Level
0.20 Rated current to 2.00 Rated cur-
rent (Heavy load)
0.20 Rated current to 1.50 Rated cur-
rent (Light load)
Rated
current of
inverter
Frequency Pull-in
Restart Parameter
Starting Frequency
Selection at
Frequency Pull-in
Restart
00: Frequency at interruption
01: Maximum frequency
02: Set frequency (Frequency refer-
ence)