Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
1st Overload Limit Parame-
ter/1st Overload Limit
Parameter 2
2nd Overload Limit Parame-
ter
0.1 to 3000.0
Set the deceleration rate for the output
frequency when the overload limit func-
tion is enabled.
Set the deceleration time from the max-
imum frequency to 0 Hz.
Multi-function Input 1 to 7
Selection
39: OLR (Overload limit switching)
*1. The Inverter speeds up in a regenerative state, only during operation. It does not speed up during deceleration.
⚫
Example case where overload limit function is activated during acceleration
(b021/b024/b221 = 01 or 03)
Overload Limit Level
b022/b025
b222
Output current
Maximum frequency
A004/A204
Deceleration caused by
Overload Limit Parameter
Set frequency
F001
Inverter output
frequency
b023/b026/b223
⚫
Example case where overload limit function is activated during deceleration
(during regeneration)
For the 3G3MX2-EV2 Series, the overload limit function does not work during deceleration stop.
Therefore, even if the output current value exceeds the overload limit level due to regeneration, the
inverter continues the deceleration stop.
Output current
Overload
Limit
Level
b022/b222,
b025
Output
frequency
7-8 Functions Related to Protection, Warning, and Various Output Signals
7-8-4 Overload Limit/Overload Warning