8 Communications Functions
8 - 55
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1240
hex
123F hex
1st Automatic
Torque Boost Volt-
age Compensation
Gain
A046
R/W
0 to 255
1 [%]
P. 5-59
1241
hex
1240 hex
1st Automatic
Torque Boost Slip
Compensation Gain
A047
R/W
0 to 255
1 [%]
1242
to
1244
hex
Reserved
1245
hex
1244 hex
DC Injection Braking
Selection
A051
R/W
00: Disabled
01: Enabled
02: Enabled (Oper-
ates only at set fre-
quency)
P. 7-93
1246
hex
1245 hex
DC Injection Braking
Frequency
A052
R/W
0 to 6000
0.01
[Hz]
1247
hex
1246 hex
DC Injection Braking
Delay Time
A053
R/W
0 to 50
0.1 [s]
1248
hex
1247 hex
DC Injection Braking
Power
A054
R/W
0 to 100 (70)
1 [%]
1249
hex
1248 hex
DC Injection Braking
Time
A055
R/W
0 to 600
0.1 [s]
124A
hex
1249 hex
DC Injection Braking
Edge/Level
Selection
A056
R/W
00: Edge operation
01: Level operation
8