8 Communications Functions
8 - 56
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
124B
hex
124A hex
Startup DC Injection
Braking Power
A057
R/W
0 to 100 (70)
1 [%]
P. 7-93
124C
hex
124B hex
Startup DC Injection
Braking Time
A058
R/W
0 to 600
0.1 [s]
124D
hex
124C hex
(Reserved)
A059
*1
R/W
20 to 150
0.1
[kHz]
124E
hex
Reserved
124F
hex
124E hex
1st Frequency
Upper Limit
A061
(HIGH)
R/W
0
1st Frequency Lower
Limit to 1st Maximum
Frequency
0.01
[Hz]
P. 5-30
1250
hex
124F hex
A061
(LOW)
R/W
1251
hex
1250 hex
1st Frequency
Lower Limit
A062
(HIGH)
R/W
0
Starting Frequency to 1st
Maximum Frequency
0.01
[Hz]
1252
hex
1251 hex
A062
(LOW)
R/W
1253
hex
1252 hex
Jump Frequency 1
A063
(HIGH)
R/W
0 to 59000
0.01
[Hz]
P. 7-36
1254
hex
1253 hex
A063
(LOW)
R/W
1255
hex
1254 hex
Jump Frequency
Width 1
A064
R/W
0 to 1000 (10000)
*2
0.01
[Hz]
1256
hex
1255 hex
Jump Frequency 2
A065
(HIGH)
R/W
0 to 59000
0.01
[Hz]
1257
hex
1256 hex
A065
(LOW)
R/W
1258
hex
1257 hex
Jump Frequency
Width 2
A066
R/W
0 to 1000 (10000)
*2
0.01
[Hz]
1259
hex
1258 hex
Jump Frequency 3
A067
(HIGH)
R/W
0 to 59000
0.01
[Hz]
125A
hex
1259 hex
A067
(LOW)
R/W
125B
hex
125A hex
Jump Frequency
Width 3
A068
R/W
0 to 1000 (10000)
*2
0.01
[Hz]
125C
hex
125B hex
Acceleration Stop
Frequency
A069
(HIGH)
R/W
0 to Starting Frequency:
Disabled
Frequency above Start-
ing Frequency to 59000
0.01
[Hz]
P. 7-37
125D
hex
125C hex
A069
(LOW)
R/W
125E
hex
125D hex
Acceleration Stop
Time
A070
R/W
0: Disabled
1 to 600
0.1 [s]