EasyManua.ls Logo

Omron MX2 Series - Page 521

Omron MX2 Series
612 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Communications Functions
8 - 77
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
143A
hex
1439 hex
Overtorque/
Undertorque
Selection
C054
R/W
00: Overtorque
01: Undertorque
P. 6-15
143B
hex
143A hex
Overtorque/
Undertorque Level
(Forward Power
Running)
C055
R/W
0 to 200
1 [%]
143C
hex
143B hex
Overtorque/
Undertorque Level
(Reverse
Regeneration)
C056
R/W
0 to 200
1 [%]
143D
hex
143C hex
Overtorque/
Undertorque Level
(Reverse Power
Running)
C057
R/W
0 to 200
1 [%]
143E
hex
143D hex
Overtorque/
Undertorque Level
(Forward
Regeneration)
C058
R/W
0 to 200
1 [%]
143F
hex
143E hex
Overtorque/
Undertorque Signal
Operation
C059
R/W
00: Enabled during
acceleration/decel-
eration and con-
stant speed
01: Enabled during
constant speed
1440
hex
Reserved
1441
hex
1440 hex
Electronic Thermal
Warning Level
C061
R/W
0 to 100
1 [%]
P. 7-77
1442
hex
Reserved
1443
hex
1442 hex
0 Hz Detection Level
C063
R/W
0 to 10000
0.01
[Hz]
P. 5-57
1444
hex
1443 hex
Cooling Fin Over-
heat Warning Level
C064
R/W
0 to 110
1 [°C]
P. 7-88
1445 to
144A
hex
Reserved
144B
hex
144A hex
Communication
Speed Selection
(Baud Rate
Selection)
C071
R/W
03 (2400 bps)
04 (4800 bps)
05 (9600 bps)
06 (19.2 kbps)
07 (38.4 kbps)
08 (57.6 kbps)
09 (76.8 kbps)
10 (115.2 kbps)
P. 8-5
144C
hex
144B hex
Communication Sta-
tion No. Selection
C072
R/W
1 to 247
144D
hex
Reserved
8
8-9 Modbus Communication Data Lists
8-9-4 Group A/b/C/H/P Register List

Table of Contents

Related product manuals