EasyManuals Logo

Omron MX2 Series User Manual

Omron MX2 Series
612 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #543 background imageLoading...
Page #543 background image
8 Communications Functions
8 - 99
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
230C
hex
230B hex
2nd Electronic
Thermal Level
b212
R/W
200 to 1000
0.1 [%]
P. 5-15
230D
hex
230C hex
2nd Electronic
Thermal
Characteristics
Selection
b213
R/W
00: Reduced torque
characteristics
01: Constant torque
characteristics
02: Free setting
230E to
2315
hex
Reserved
2316
hex
2315 hex
2nd Overload Limit
Selection
b221
R/W
00: Disabled
01: Enabled during
acceleration and
constant speed
02: Enabled during
constant speed
03: Enabled during
acceleration and
constant speed
(Accelerated
during regenera-
tion)
P. 7-78
2317
hex
2316 hex
2nd Overload Limit
Level
b222
R/W
100 to 2000 (1500)
0.1 [%]
2318
hex
2317 hex
2nd Overload Limit
Parameter
b223
R/W
1 to 30000
0.1 [s]
2319
to
2428
hex
Not used
Not accessible
2429
hex
2428 hex
2nd Overload
Warning Level
C241
R/W
0 to 2000
0.1 [%]
P. 7-78
242A to
2501
hex
Not used
Not accessible
2502
hex
2501 hex
2nd Motor Parame-
ter Selection
H202
R/W
00: Standard motor
parameter
02: Auto-tuning param-
eter
P. 6-4
2503
hex
2502 hex
2nd Motor Capacity
H203
R/W
00: 0.1
01: 0.2
02: 0.4
03: 0.55
04: 0.75
05: 1.1
06: 1.5
07: 2.2
08: 3.0
09: 3.7
10: 4.0
11: 5.5
12: 7.5
13: 11.0
14: 15.0
15: 18.5
8
8-9 Modbus Communication Data Lists
8-9-5 2nd Control Register Number List

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC

Related product manuals