143
Bits
can be programmed to turn ON and
OFF at regular intervals while a desig
-
nated
execution condition is ON by using TIM twice. One TIM functions to turn
ON
and OFF a specified bit, i.e., the Completion Flag of this TIM turns the speci
-
fied
bit ON and OFF
.
The other TIM functions to control the operation of the first
TIM, i.e., when the first TIM’s Completion Flag goes ON, the second TIM is
started and when the second TIM’s Completion Flag goes ON, the first TIM is
started.
00000
TIM 002
TIM 001
TIM 001
00205
00000
00205
1.5 s
1.0 s
1.5 s
1.0 s 1.5 s1.0 s
TIM 001
#0010
TIM 002
#0015
Address Instruction Operands
00000 LD 00000
00001 AND TIM 002
00002 TIM 001
# 0010
00003 LD TIM 001
00004 TIM 002
# 0015
00005 LD TIM 001
00006 OUT 00205
A
simpler but less flexible method of creating a flicker bit is to AND one of the SR
area clock pulse bits with the execution condition that is to be ON when the
flicker
bit is operating. Although this method does not use TIM, it is included here
for comparison. This method is more limited because the ON and OFF times
must
be the same and they depend on the clock pulse bits available in the SR
area.
In
the following example the 1-second clock pulse is used (25502)
so that 00206
would
be turned ON and OFF every second, i.e., it would
be ON for 0.5 seconds
and OFF for 0.5 seconds. Precise timing and the initial status of 00206 would
depend on the status of the clock pulse when 00000 goes ON.
00000 25502
00206
Address Instruction Operands
00000 LD 00000
00001 LD 25502
00002 OUT 00206
5-14-2 HIGH-SPEED TIMER – TIMH(15)
N: TC number
# (000 through 015 preferred)
Ladder Symbol
Definer Values
SV: Set value (word, BCD)
IR, AR, DM, HR, LR, #
Operand Data Areas
TIMH(15) N
SV
Limitations SV
is between 00.00 and 99.99. (Although 00.00 and 00.01 may be set, 00.00
will
disable the timer
, i.e., turn ON the Completion Flag immediately
, and 00.01
is
not reliably cycled.) The decimal point is not entered.
Example 5:
Flicker Bits
Timer and Counter Instructions Section 5-14

Table of Contents

Other manuals for Omron SYSMAC C200HS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C200HS and is the answer not in the manual?

Omron SYSMAC C200HS Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C200HS
CategoryController
LanguageEnglish

Related product manuals