388
4. Turn on the CPU.
5. If
the desired program or UM Area
data is not already in the CPU, write the
data or transfer it to the CPU.
6. Switch the C200HS to PROGRAM mode.
7. Turn
ON SR 27000 from
the LSS or a Programming Console. The UM Area
data will be written to the Memory Card and SR 27000 will be turned OFF
automatically.
Reading Data The
following procedures
are used to read UM Area data from a Memory Cas
-
sette
mounted in the C200HS CPU to the CPU. This can be achieved either au
-
tomatically
when the C200HS is turned on or manually from a Programming
De
-
vice.
Automatic Reading at Startup
1, 2, 3... 1. Turn ON pin 2 on the CPU’s DIP switch to enable reading at startup.
2. Make sure that power to the C200HS CPU is turned OFF.
3. Mount the Memory Cassette containing the data to be read to the CPU.
4. Turn
on the CPU. The data in
the Memory Cassette will be read to the CPU.
Manual Reading
1, 2, 3... 1. Make sure that power to the C200HS CPU is turned OFF.
2. Mount the Memory Cassette containing the data to be read to the CPU.
3. Turn on the CPU.
4. Switch the C200HS to PROGRAM mode.
5. Turn
ON SR 27001 from the LSS or a Programming Console. The data in the
Memory
Cassette will be read to the CPU and SR 27001 will be turned OFF
automatically.
Comparing Data The
following procedure is used to compare the UM Area data in a Memory
Cas
-
sette to the UM Area data in the CPU.
1, 2, 3... 1. Make sure that power to the C200HS CPU is turned OFF.
2. Mount the Memory Cassette containing the data to be compared.
3. Turn on the CPU.
4. Switch the C200HS to PROGRAM mode.
5. Turn
ON SR 27002 from the LSS or a Programming Console. The data in the
Memory
Cassette will be compared to the data in CPU and SR 27002 will be
turned OFF automatically.
6. Read
the status of SR 27003 to determine the
results of the comparison. If
SR
27003 is OFF
, the data in the Memory Cassette
is the same as that in the
CPU.
If SR 27003 is ON,
either the data is dif
ferent or the C200HS was not in
PROGRAM mode when the operation was performed.
Note 1. SR 27003 is used only to show the results of comparisons and cannot be
manipulated by the user.
2. If the comparison operation is executed in any but PROGRAM mode, SR
27002
will
turn ON, as will SR 27003. In this case, the status of SR 27003 will
be meaningless.
3. SR 273003 will turn ON if the comparison operation is used without a
Memory Cassette mounted to the CPU.
9-4 IOM Area Data
The
following procedures can be used to read IOM data from and
write IOM data
to an EEPROM Memory Cassette mounted to a C200HS CPU. IOM data in-
cludes
IR 000 to IR 231, the two work areas, the two SR Areas, the LR Area, the
HR
Area, the AR Area, the TC Area, and DM 0000 to DM 6143. This procedure
cannot
be used to write to
EPROM Memory Cassettes, which require a PROM
writer. Refer to the LSS operation manuals for PROM writer procedures.
IOM Area Data Section 9-4

Table of Contents

Other manuals for Omron SYSMAC C200HS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C200HS and is the answer not in the manual?

Omron SYSMAC C200HS Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C200HS
CategoryController
LanguageEnglish

Related product manuals