Data table settings
S
S+2
S+4
S+6
S+8
K0
S+2n
S+2(n+1)
S+2(n+2)
Control code
Frequency 1
(Pulse number)
Frequency 2
Target value 1
(Pulse number)
Target value 2
Frequency n
(Pulse number)
Target value n
Operand Settings Description
(1) S Control code
Specify the control code by setting the H constant.
Output method
0: Addition counting CW
Operation mode
Frequency range
Not used
Duty (on width)
0: Duty 1/2 (50%)
0: Fixed
0: Specify Incremental movement amount (pulse no.).
1: Specify Absolute target value (absolute value).
1: Duty 1/4 (25%)
1: Subtraction counting CCW
2: Addition counting PLS+SIGN (forward off)
3: Subtraction counting PLS+SIGN (reverse on)
4: Addition counting PLS+SIGN (forward on)
5: Subtraction counting PLS+SIGN (reverse off)
H
(2)
S+2,
S+2n
Frequency n
The setting range of the settable maximum speed varies according to
the setting of the initial speed as shown in the table below.
Range Initial speed Maximum speed
Low
speed
K1 to K49
(1 to 49 Hz)
Initial speed to K22000 (to 22
kHz)
7.2 FP-X Compatible Instruction Mode Control Instruction