2.2 Connection with Stepping Motor Driver
2.2.1 Precautions on Connection
Connections of various signals
Signal type Point
Pulse command output
Connect the output allocated to each channel and the command pulse input of
motor driver.
Use twisted-pair cables for the connection.
Use a 24 V DC input for the input on the driver side. When the input interface of
the driver is 5 V DC input, insert a resistor for limiting currents externally.
Home input
Connect the input allocated to each channel and the home sensor.
Use twisted-pair cables for the connection.
Near home input
Connect the near home sensor to an arbitrary input.
It will be valid when the outputs (Y70 to Y75) allocated to each channel in user
programs turn ON.
CCW over limit input Connect the over limit switches to arbitrary inputs.
It will be valid when the outputs (Y80 to Y8B) allocated to each channel in user
programs turn ON.
CW over limit input
Use twisted-pair cables for the connection between the output of the unit and motor driver.
2.2 Connection with Stepping Motor Driver
2-4 WUME-FPXHPOSG-01