REFERENCE
11.2.2 When Using Pulse Output Function (FP-X Compatible Instruction Mode)
7.2.4 [F174 (SP0H)] Pulse Output (Selectable Data Table Control Operation)
This instruction outputs pulses from a specified pulse output channel according to a specified
data table.
Instruction format
Operand
Operand Settings
S Starting number of the area in which data tables are registered
n Target channel for pulse output
Memory area type that can be specified
Operand
WX WY WR WL SV EV DT LD I
Constant
Index
modifier
K H
S - - - - - - - - - -
n - - - - - - - - - -
Outline of operation
Outputs pulses from a specified channel according to the settings specified in the data table
starting with the address specified by [S] when a corresponding control active flag is OFF
and the execution condition is ON.
Switches the pulse frequency when the elapsed value of the high-speed counter reaches the
target value set in the data table. (It is performed by the interrupt processing.)
Stops the pulse output when the elapsed value reaches the final target value.
For setting the frequency to 50 kHz or more, specify the duty of 1/4 (25%).
7.2 FP-X Compatible Instruction Mode Control Instruction