When the frequency after the second step is 0 or outside of the settable range, the pulse
output stops.
When the table pointer exceeds the area of data registers DT during the pulse output, the
pulse output control will be canceled and the control active flag will turn OFF.
The target values should be set in the range shown on the next page. If a value outside of
the range is specified, the number of pulses different from the specified value is output.
For details of the allocations of I/O and flags, refer to “Allocation of Memory Areas”.
REFERENCE
11.2.2 When Using Pulse Output Function (FP-X Compatible Instruction Mode)
7.2.5 [F175 (SPSH)] Pulse Output (Linear Interpolation)
Pulses are output from channel for 2 pulse output, in accordance with the parameters in the
designated data table, so that the path to the target position forms a straight line.
Instruction format
Operand
Operand Settings
S Starting number of the area in which data tables are registered
n 0 or 2
Memory area type that can be specified
Operand
WX WY WR WL SV EV DT LD I
Constant
Index
modifier
K H
S - - - - - - - - - -
n - - - - - - - - - -
Outline of operation
Outputs pulses from a specified channel when a corresponding control active flag is OFF
and the execution condition is ON.
The control code, initial speed, maximum speed, acceleration / deceleration time, and target
value are specified by creating data tables [S] to [S+11] described on the next page using a
user program.
7.2 FP-X Compatible Instruction Mode Control Instruction
7-26 WUME-FPXHPOSG-01