4-44
Default: [ ]
Pr4.21
Analog monitor output setup
Range Unit Default
Related
control mode
0 to 2 — 0 P S T F
Select output format of the analog monitor.
Setup value Output format
[0] Signed data output –10 V to 10 V
1 Absolutevaluedataoutput 0Vto10V
2 Dataoutputwithoffset 0Vto10V(5Vatcenter)
Pr4.22
Analog input 1 (AI1) offset setup
Range Unit Default
Related
control mode
−5578to5578 0.359 mV 0 P S T F
Setuptheoffsetcorrectionvalueappliedtothevoltagefedtotheanaloginput1.
Pr4.23
Analog input 1 (AI1) filter
Range Unit Default
Related
control mode
0 to 6400 0.01 ms 0 P S T F
Setupthetimeconstantof1stdelaylterthatdeterminesthelagtimebehindthevoltage
applied to the analog input 1.
Pr4.24
Analog input 1 (AI1) overvoltage setup
Range Unit Default
Related
control mode
0 to 100 0.1 V 0 P S T F
Setuptheexcessiveleveloftheinputvoltageofanaloginput1byusingthevoltage
associatedwithoffset.
Pr4.25
Analog input 2 (AI2) offset setup
Range Unit Default
Related
control mode
−342to342 5.86 mV 0 P S T F
Setuptheoffsetcorrectionvalueappliedtothevoltagefedtotheanaloginput2.
Pr4.26
Analog input 2 (AI2) filter
Range Unit Default
Related
control mode
0 to 6400 0.01 ms 0 P S T F
Setupthetimeconstantof1stdelaylterthatdeterminesthelagtimebehindthevoltage
applied to the analog input 2.
Pr4.27
Analog input 2 (AI2) overvoltage setup
Range Unit Default
Related
control mode
0 to 100 0.1 V 0 P S T F
Setuptheexcessiveleveloftheinputvoltageofanaloginput2byusingthevoltage
associatedwithoffset.
Pr4.28
Analog input 3 (AI3) offset setup
Range Unit Default
Related
control mode
−342to342 5.86 mV 0 P S T F
Setuptheoffsetcorrectionvalueappliedtothevoltagefedtotheanaloginput3.
1. Details of parameter
[Class 4] I/F monitor setting