EasyManua.ls Logo

PENKO 1020 - Page 54

PENKO 1020
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.1.2. Menu Settings -System Setup - Indicator Setup - continue-
1020 Indicator
Set the input range for load cells. Choose between 1 mV/V, 1.5 mV/V, 2 mV/V,
2.5 mV/V and 3 mV/V.
When using a theoretical calibration, note that the 2mV/V and 3mV/V range are
calibrated ranges.
Set an ADC value offset. This can be used when the weigher gets out of its ADC
range. Choose a value between500000 and +500000.
For more information, contact PENKO.
Recall
This menu allows to set all indicator parameter back to factory settings.
Note: the calibration values remain in the indicator memory.
Enter the TAC code to enter the menu.
Enter TAC (number) by using the UP key
and confirm with Enter.
TAC (Traceable Access Code) shows on the lower right of the screen. Every time
settings are changed, the TAC code automatically levels up by 1.
Example TAC:2
TAC Code
54

Table of Contents

Related product manuals