5.9. What to do if things go wrong
Module Status LEDs Blinking Green with unexpected results
• Check that all sensors are operational and that all zones are clear then perform procedure again.
How to change block/clear sensor logic without having to perform another Auto-Configuration
• Check all network and power connections and make sure there is 24V on each Ai2 Module then
try the Auto-Configuration procedure again
• Verify that all of the module sensor/motor combinations are valid. Check here to find out what
module set-ups will generate errors
Module Status LED is Blinking or Flashing Red
• Make sure there are no other Ethernet devices (PC’s, Switches, Scanners, etc.) connected
between any of the module on your network. The Auto-Configuration procedure aborts when it
encounters a non ConveyLinx device along the network path before reaching the last module. Ai2
Modules up to that point should be configured properly but the remaining modules will not.
• When removing a Ai2 Module from an existing configured network that is already operational; be
sure to wait 1 or 2 minutes to allow the Ethernet Switches on the modules to reset their MAC
Address ARP table before attempting a new Auto-Configuration procedure