5.9. What to do if things go wrong
Module Status LEDs Blinking Green with unexpected results
Check that all sensors are operational and that all zones are clear then perform procedure again.
How to change block/clear sensor logic without having to perform another Auto-Configuration
Check all network and power connections and make sure there is 24V on each Ai2 Module then
try the Auto-Configuration procedure again
Verify that all of the module sensor/motor combinations are valid. Check here to find out what
module set-ups will generate errors
Module Status LED is Blinking or Flashing Red
Make sure there are no other Ethernet devices (PC’s, Switches, Scanners, etc.) connected
between any of the module on your network. The Auto-Configuration procedure aborts when it
encounters a non ConveyLinx device along the network path before reaching the last module. Ai2
Modules up to that point should be configured properly but the remaining modules will not.
When removing a Ai2 Module from an existing configured network that is already operational; be
sure to wait 1 or 2 minutes to allow the Ethernet Switches on the modules to reset their MAC
Address ARP table before attempting a new Auto-Configuration procedure
Last modified: Aug 04, 2020
PULSEROLLER ConveyLinx-Ai2 User's Guide - 1.7
Page 54 of 154

Table of Contents

Other manuals for Pulseroller ConveyLinx-Ai2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulseroller ConveyLinx-Ai2 and is the answer not in the manual?

Pulseroller ConveyLinx-Ai2 Specifications

General IconGeneral
BrandPulseroller
ModelConveyLinx-Ai2
CategoryControl Unit
LanguageEnglish