7.2.1.4. Induct Forward Time/Distance
Induct Forward value is used to cause the MDR to continue to run after the zone’s photo-sensor has been
blocked when receiving a carton from upstream.
This value is adjustable per zone to
compensate for special conditions when for
example a zone’s photo-sensor needs to
be placed farther upstream from the
discharge end of the zone
Induct Forward Time
Enter new values for upstream and/or
downstream Induct Forward time and
click the corresponding Set button. The
default is 0 seconds and the valid range is
0 to 65 seconds. The Set All button will
apply these same settings for the range of
modules indicated at the top of the dialog.
In this example we are changing the
Induct Forward time to 1.00 seconds for
both the upstream and downstream
zones and updating this setting to Nodes
3 thru 4
PULSEROLLER ConveyLinx-Ai2 User's Guide - 1.7
Page 109 of 154