7.2.1.2. Jam & Auto Clear Timers
The Jam Timer for a given Upstream or Downstream zone is used for both detecting an Arrival Jam and a
Sensor Jam. The Jam Timer should be set as the maximum expected time it takes for a carton to travel
from one zone to the next plus a small addition to prevent nuisance jam occurrences. The default value for
the Jam Timer is 5 seconds and the valid range of values is from 1 seconds to 65 seconds.
The Auto Clear Timer is the amount of times that the logic maintains the jam condition before auto
resetting the jam. The default value for the Auto Clear Timer is 5 seconds and the valid range of values is
from 0 seconds to 65 seconds
Enter new values for either or both the
Jam Timer and/or Auto Clear Timer and
click the corresponding Set button for
each. The Set All button will apply these
same settings for the range of modules
indicated at the top of the dialog