Using the Configurator
19.46 Configuring suite silence
To configure suite silence
1. Select Job Details in the job tree.
2. Set the Alert rate to Alert and the Evac rate to Temporal.
3. If the job has audio, click the Set up button under Audio. Click the buttons beside Alert
and Evac and set the alert rate to Alert and the Evac rate to Temporal.
4. Set New Alarm to 60 seconds. After 60 seconds, the signals will stop in the correlated
zones, except the zone where the alarm was initiated.
5. Set Auto Resound to 10 minutes. After 10 minutes, the alarm will sound in all the suites
if it has not been acknowledged.
6. Set Signal Silence Inhibit to 60 seconds.
7. Set Auto Signal Silence to Disabled.
Figure 152 Timers for suite silence
8. Create an alarm zone for each floor.
9. Create 2 signal circuits for each floor - one circuit for the suites, and one for the hallways.
10. Correlate each floor alarm zone to the corresponding suite's signal circuits.
11. Correlate Common Alarm to the Hallways' signal circuits.
12. Correlate the Common Alarm common system status to the hallways' signal circuits.
13. Correlate the New Alarm Active common system status to all suite signal circuits.
14. Correlate the Auto Suite Resound common system status to all suite signal circuits.

Table of Contents

Other manuals for Secutron MMX-2009-12NDS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MMX-2009-12NDS and is the answer not in the manual?

Secutron MMX-2009-12NDS Specifications

General IconGeneral
BrandSecutron
ModelMMX-2009-12NDS
CategoryControl Panel
LanguageEnglish

Related product manuals