Table 86: MS LED on the FX3-XTDI I/O module
MS LED Meaning Notes
o
Supply voltage out of range Switch on the voltage supply of the Flexi Soft sys‐
t
em and check at the A1 and A2 terminals of the
main module.
Ö R
ed/
green (1Hz)
With firmware V1.xx.0: invalid
conf
iguration
With firmware ≥V2.00.0:
remediable external error
Check cabling of the flashing inputs.
If all output LEDs are flashing, check the supply
voltage of terminals A1 and A2 on this module.
Ö Gr
een
(1Hz)
System in Stop The application can be started from within the
conf
iguration software.
O Gr
een
System in Run
Ö R
ed
(1Hz)
With firmware V1.xx.0: reme‐
diable e
xternal error
Check cabling of the flashing inputs
With firmware ≥ V2.00.0:
invalid configuration
Ö R
ed
(2Hz)
Serious error in the system,
pr
esumably in this module.
The application was stopped.
Switch thepower supply off and then on again.
If the problem still has not been remedied after
multiple repetitions, replace this module.
Use the configuration software diagnostic func‐
tion.
O R
ed
Serious error in the system,
pr
esumably in a different
module. The application was
stopped.
Switch thepower supply off and then on again.
If the problem still has not been remedied after
multiple repetitions, replace the module showing
Ö red (2Hz). If applicable, also use the diag‐
nostic function in the configuration software to
isolate the affected module.
Table 87: Input LEDs on the FX3-XTDI I/O module
Input LEDs (I1 … I8) Meaning
o
Input is deactivated.
O Gr
een
Input is active.
Ö Gr
een (1Hz) synchronized with the red
MS LED
Input is deactivated and there is a remediable
er
ror.
Ö Gr
een (1Hz) alternating with the red MS
LED
Input is active and there is a remediable error.
NOTE
T
he LEDs indicate the state and are updated approx. every 64 ms.
8.4 Status messages for the FX3-XTDS I/O module
For information on the positions of the LEDs on the FX3-XTDS I/O module, see
f
igure 33, page 58.
OPERATION 8
8012478/1IG6/2023-02-24 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller
109
Subject to change without notice