Table 92: Statuses indicated by the MS LED on the FX3-ANA0 analog input module
MS LED Meaning Notes
o
Supply voltage out of range Switch on the voltage supply of the Flexi Soft sys‐
t
em and check at the A1 and A2 terminals of the
main module.
Ö R
ed/
green (1Hz)
Remediable external error Check cabling of the flashing inputs
Ö Gr
een
(1Hz)
System in Stop status The application can be started using the configu‐
r
ation software.
O Gr
een
System in Run status
Ö R
ed
(1Hz)
Invalid configuration
Ö R
ed
(2Hz)
Serious error in the system,
pr
obably in this module. The
application was stopped. All
outputs are switched off.
Switch thevoltage supply off and then on again.
If the problem still has not been remedied after
multiple repetitions, replace this module.
Use the configuration software diagnostic func‐
tion.
O R
ed
Serious error in the system,
pr
obably in a different mod‐
ule. The application was stop‐
ped. All outputs are switched
off.
Switch thevoltage supply off and then on again.
If the problem still has not been remedied after
multiple repetitions, replace the module showing
Ö red (2Hz). If applicable, also use the diag‐
nostic function in the configuration software to
isolate the affected module.
Table 93: Statuses indicated by the input LEDs on the FX3-ANA0 analog input module
Input LEDs AI1, AI2 Meaning
o
Input is deactivated.
O Green
Input is active.
Ö Gr
een (1Hz) synchronized with the Ö
red/green MS LED (1Hz)
Input is deactivated and there is a remediable
er
ror.
8.7 Status messages of the FX3-MOCx motion control module
For information on the position of the LEDs on the FX3-MOCx motion control module,
see
figure 35, page 59.
8 O
PERATION
112
O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller 8012478/1IG6/2023-02-24 | SICK
Subject to change without notice