Configuration
WARNING
Ine
ffectiveness of the protective device due to incorrect configuration
The dangerous state may not be stopped or not be stopped in a timely manner in the
event of non-compliance.
The target safety-related level may not be achieved in the event of non-compliance.
►
Check whether the configured safety application monitors the machine or plant
as intended and if the safety of the configured application is maintained at all
times. This must be ensured in every operating mode and secondary application.
Document the results of this thorough check.
►
Check the safety function again after any change to the configuration.
►
Observe the testing information in the operating instructions for the connected
protective devices.
Repairs and modifications
DANGER
Im
proper work on the product
A modified product may not offer the expected protection if it is integrated incorrectly.
►
Apart from the procedures described in this document, do not repair, open, manip‐
ulate or otherwise modify the product.
2.2 Intended use
The Flexi Soft modular safety controller is an adjustable control for safety applications.
It is t
o be used in accordance with the following standards:
•
IEC 61508 and IEC 62061 up to SIL3
•
ISO 13849 up to performance level e
The safety level actually achieved is determined by the external wiring, how the wiring
is implemented, the configuration, the selection of command triggers, and how they are
arranged on the machine.
The product may be used in safety functions.
The product must only be used within the limits of the prescribed and specified techni‐
cal specifications and operating conditions at all times.
Incorrect use, improper modification or manipulation of the product will invalidate any
warranty from SICK; in addition, any responsibility and liability of SICK for damage and
secondary damage caused by this is excluded.
The product is only suitable for use in industrial environments.
UL/CSA applications:
If t
he product is being used in accordance with UL508 or CSA C22.2No.142, the
following conditions must also be met:
•
To protect the device’s 24-volt voltage supply, use a fuse with a maximum voltage
of 4A and a minimum of 30VDC in accordance with UL248.
•
For wiring, only use copper wires with a temperature resistance of at least
60°C/75°C, wire cross-section AWG30–12 for screw terminals and/or
AWG24–16 for spring terminals.
•
Tighten the screw terminals with a torque of 5 to 7lb-in.
•
Only use the devices in an environment with maximum degree of contamination2.
2 S
AFETY INFORMATION
12
O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller 8012478/1IG6/2023-02-24 | SICK