14
These are parameters of the SSI encoder that can be set in Flexi Soft Designer.
15
Plus the resolution of the speed information based on the resolution of the encoder system:
a)
Rotational movement in rpm = 15,000/(increments per revolution)
b) Linear movement in mm/s = 250/(increments per revolution)
16
Plus the resolution of the position information based on the resolution of the encoder system:
1rev./(increments per revolution).
17
Peak-to-peak voltage between ENCx_y+ and ENCx_y–.
18
Voltage between ENCx_y+ and ENC_0V as well as between ENCx_y– and ENC_0V.
19
For a description of this function, refer to the “Sine-cosine analog voltage monitoring” section in the “Flexi
Soft in the Flexi Soft Designer Configuration Software” operating instructions.
20
Plus the resolution of the speed information based on the resolution of the encoder system:
a) Rotational movement in rpm = 15,000/(4xnumber of sine-cosine periods per revolution)
b) Linear movement in mm/s = 250/(4 × number of sine-cosine periods per revolution)
21
Plus the resolution of the position information based on the resolution of the encoder system:
1rev./(4xnumber of sine-cosine periods per revolution).
22
Firmware version ≥V1.10.0. With earlier firmware versions 16...32bits.
23
Firmware version ≥V1.10.0. With earlier firmware versions 16...62bits.
24
If the maximum permissible change to the position information (speed)is exceeded, then this can lead
to the output of an inverted rotation direction and to a lower speed, since it results in non-recognized
overflowing of the position data bits.
Mechanical data
T
able 167: Mechanical data MOC0
MOC0
Dimensions (W × H × D) 22.5 × 96.5 × 126.2mm
Weight 120g
Ambient data
T
able 168: Ambient data MOC0
MOC0
Enclosure rating (IEC60529) IP20
Ambient operating temperature
(UL/C
SA: surrounding air tempera‐
ture)
-25 ... +55°C
Storage temperature -25 ... +70°C
Air humidity ≤95%, non-condensing
Operating altitude Max. 2,000m above sea level (80kPa)
Vibration resistance 5–150Hz/1G (EN60068-2-6)
10–500Hz/3G
r
ms
(EN60068-2-64)
Shock resistance, continuous shock 15g, 11ms (EN 60068-2-27)
Shock resistance, single shock 30g, 11ms (EN 60068-2-27)
12.3.8 Motion Control MOC1
Safety-related parameters
T
he data apply to an ambient temperature of +40°C.
Table 169: Safety-related parameters MOC0
MOC1
Safety-related parameters for axes with two encoders (any combination of sine-cosine, TTL,
H
TL24V, HTL12V, RS-422, SSI, same or different types)
Safety integrity level (IEC61508)
Safety integrity level (IEC62061)
SIL 3
Category(ISO13849) Category 4
Performance level (ISO13849) PL e
TECHNICAL DATA 12
8012478/1IG6/2023-02-24 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller
159