16.3 Checklist for the manufacturer
Checklist for manufacturers / installers for the installation of the Flexi Soft safety
c
ontroller
The details on the items listed below must be available at the latest when the system is
commissioned for the first time. However, they are dependent upon the application, the
requirement of which must be reviewed by the manufacturer/installer.
This checklist should be retained and kept with the machine documentation to serve as
reference during recurring tests.
This checklist does not replace the initial commissioning, nor the regular inspection by
qualified safety personnel.
Have the safety rules and regulations been observed in compliance with the
dir
ectives/standards applicable to the machine?
Yes No
Are the applied directives and standards listed in the declaration of con‐
f
ormity?
Yes No
Does the protective device correspond to the required category? Yes No
Are the required protective measures against electric shock in effect (protec‐
t
ion class)?
Yes No
Has the safety function been checked in compliance with the test notes of
t
his documentation? In particular:
Function test on the control switches, sensors and actuator connected to
the safety controller
Check of all cut-off paths
Yes N
o
Is it ensured that a complete test of the safety functions is done after any
conf
iguration change of the safety controller?
Yes No