LED display on the module Possible error
c
odes
Possible causes Possible measures
Main module
FX3-
CPUx
Expansion
module
1)
MS = O gr
een
All expansion
module
s:
MS = O green
Main module:
0x000A0011
F
unction block error during
dual-channel input evaluation
(e.g., emergency stop, solenoid
switch): discrepancy error at
input pair 1 of the function block
Cable break or short-circuit to
GND at one of the two input sig‐
nals of the input pair
Sensor hardware error (e.g., is
one of the two contacts/outputs
permanently closed (High) or
open (Low)).
Defective sensor (one of the two
signals is not switching to a
state corresponding to the other
input within the configured dis‐
crepancy time).
The safety door opened or closed
too slowly; as a result, both
contact switches (e.g., reed con‐
tacts) did not switch within the
configured discrepancy time.
Check the wiring of the affected
input and check the switching
capacity of the two contacts/out‐
puts of the connected sensor.
Check the mechanical depend‐
ence of the two switches.
Replace the switch/sensor in the
hardware installation.
To reset the error, the affected input
pair must switch from Low/Low to
High/High in the case of equivalent
dual-channel inputs and from Low/
High to High/Low in the case of
complementary dual-channel inputs
within the configured discrepancy
time.
Main module
0x00100011
F
unction block error (external
device monitoring or valve moni‐
toring): The feedback signal was
not sent in response to the con‐
trol signal within the maximum
feedback delay time.
Hardware error affecting the con‐
nected relay/valve or error in the
wiring
The relay/valve used has a lon‐
ger switching delay at the moni‐
toring contact.
Increase the maximum feedback
delay time for the function block
if this is compatible with your
application.
Replace the relay/valve in the
hardware installation.
10 TROUBLESHOOTING
124
O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller 8012478/1IG6/2023-02-24 | SICK
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK FX0-GMOD and is the answer not in the manual?

SICK FX0-GMOD Specifications

General IconGeneral
BrandSICK
ModelFX0-GMOD
CategoryController
LanguageEnglish

Related product manuals