Functions > Control > 79 > 79EF
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
EF Protection Trip 1 Inst
Delayed
Inst
EF Protection Trip 2 Inst
Delayed
Inst
EF Protection Trip 3 Inst
Delayed
Delayed
EF Protection Trip 4 Inst
Delayed
Delayed
EF Protection Trip 5 Inst
Delayed
Delayed
EF HS Trips <none>
50G-n
50N-n
51G-n
51N-n
<none>
EF Delayed Trips <none>
50G-n
50N-n
51G-n
51N-n
<none>
EF HS Trips to LO Target
EF Delayed Trips to LO
Target
Functions > Control > 79 > 79GS
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
GS Triggers 50GS-n
51GS-n
<all>
GS Trips to LO Target 5
GS Deadtime 1 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
GS Deadtime 2 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
GS Deadtime 3 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
Delayed
5 s
Control Functions
7.3 79 Automatic Reclosing
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 435
C53000-G7040-C014-1, Edition 11.2019