EasyManua.ls Logo

Siemens 7SR51 - Page 492

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
phase polarizing voltage. This measurement is greatly simplified if the polarizing reference voltage is set to 0°
and the current phase angle is measured with respect to this reference.
Alternatively, the instrument can be checked at the 4 points marked a, b, c & d on Figure 9-4 only.
Forward Reverse
Lag (point C) Lead (point A) Lead (point B) Lag (point D)
Pick-up Drop-off Pick-up Drop-off Pick-up Drop-off Pick-up Drop-off
MTA MTA -85 MTA +85 MTA -85 MTA -85
Phase A
Phase B
Phase C
[dw_7SR5_function67FunctionalTests, 1, en_US]
Figure 9-4 Directional Phase Fault Boundary System Angles
5. With the instrument reading Fwd or Rev, reduce the voltage until the element resets. Record the minimum
phase-phase operate voltage.
Minimum Voltage Setting
Measured
2 Out Of 3 Logic
Ensure that at least 1 Phase Overcurrent element is set to Directional. Apply balanced nominal
voltage. Apply current at a level above the 50/51 setting on phase A only at the characteristic angle for
forward operation, normally 45° lagging. Ensure no Directional Phase Overcurrent element opera-
tion occurs. Note that non-directional Phase Overcurrent and non-direction Earth Fault elements may
operate unless disabled.
Repeat the test with phase A current as above but also with equal current in the B phase at 180° to that in the
A phase.
Functional Tests
9.9 Protection Functional Tests
492 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals