Communications 9810 series - User manual
119 7EN05-0390-08
You can enter up to four IP addresses for SNMP trap notification for generic and enterprise-
specific traps. For enterprise traps, you must also define the number of events or maximum time
delay before SNMP traps are sent to the NMS.
SNMP trapping is only supported on SNMP v2.
Configuring SNMP using ION Setup
You can enable SNMP and configure SNMP trapping using ION Setup.
Download the ION MIB file from www.usa.siemens.com/pds.
To configure SNMP using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Communications > Advanced Ethernet > SNMP.
4. Configure your meter’s SNMP parameters by selecting the parameter and clicking Edit.
Click OK in the editing screen to set the parameter value.
Parameter Description
Enable SNMP Enables or disables SNMP on your meter.
Enable Traps Enables or disables SNMP trapping on your meter.
Trap Rcvr1 Addr to Trap
Rcvr4 Addr
Enter up to four trap receiver IP addresses where trap
messages will be sent.
Read only community
Enter the community string used for SNMP get (read-only)
requests.
Read write community
Enter the community string used for SNMP set (read/write)
requests.
Note: You can use the read/write community string for SNMP
get (read-only) requests.
System contact Enter the name of your SNMP system administrator.
System name Enter a descriptive name for your meter.
System location Enter your meter’s location.
5. Review the rest of the SNMP information and modify if necessary.
Configuring SNMP using webpages
You can configure SNMP trapping using your meter’s webpages.
Download the ION MIB file from www.usa.siemens.com/pds.
1. Connect to your meter’s webpages.
2. Go to Setup > SNMP Parameters.