Maintenance
Maintenance overview
The meter does not contain any user-serviceable parts. If the meter requires service, contact your
local Siemens Industry Technical Support representative.
NOTICE
METER DAMAGE
Failure to follow these instructions can result in equipment damage.
•
Do not open the meter case.
•
Do not attempt to repair any components of the meter.
Do not open the meter. Opening the meter voids the warranty.
Editing accumulated energy values using ION Setup
You can edit energy values such kWh and kVARh using ION Setup.
NOTE: Ensure you have recorded accumulated energy values before upgrading your meter’s
firmware. You can then re-enter these values after the upgrade.
NOTE: Revenue-locked meters must be unlocked before accumulated energy values can be
edited. See "Revenue locking your meter" on page 279 for more information
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Template.
4. Click the Register Edit tab, click Energy then click Display. Enter your meter’s password (if
prompted) and click OK.
The Register Editor screen displays.
5. Click Edit to enable editing.
6. Enter values for kWh, kVAh and kVARh as required. Click Send to finish.
NOTE: Only values that have the check box selected will be sent to the meter.
7. Click Close to close the Register Editor screen.
Test mode
Test mode is typically used for verifying meter functions.