Cable type
CAT5 (or higher). Use with unshielded RJ45 modular
connector
Cable length 100 m (330 ft) maximum
Connection type Direct, point-to-point
Environment
Operating temperature –20 ºC to 60 ºC (–4 ºF to 140 ºF)
Storage temperature –40 °C to 85 °C (–40 °F to 185 °F)
Humidity rating
5%–95% RH non-condensing
Maximum dewpoint: 37 °C (99 °F)
Pollution degree 2
Altitude < 3000 m (9843 ft) above sea level
IP degree of protection
Front: IP65
Rear: IP30
Location/mounting
For UL Type 12 applications, install display on a flat surface
of a Type 12 enclosure
Not suitable for wet locations
For indoor use only
Option modules
See your option module’s installation guide for additional option module specifications.
Maximum number of modules 4
Input resistance
< 300 Ω (current mode)
> 500 kΩ (voltage mode)
Input voltage mode 0–30 V DC
Input current mode 4–20 mA , 0–20 mA
Operating temperature
–25 to 70 ºC (–13 to 158 ºF)
Maximum operation temperature is based on the quantity and
type of attached option modules.
US2:948M2AO4AI Analog (2 out, 4 in)
Maximum number of modules 4
Operating temperature
–25 to 70 ºC (–13 to 158 ºF)
Maximum operation temperature is based on the quantity and
type of attached option modules.
US2:948M2DO6DI Digital (2 out, 6 in)
9810 series - User manual 9810 specifications