Logging 9810 series - User manual
237 7EN05-0390-08
A Log buffer
B Long-term memory
C Record that cannot be logged because log buffer is full (this record is lost)
D Record moving from short-term memory to long-term memory
E New record at next interval
Changing log interval and depth settings using ION Setup
You can configure log intervals, log depths and buffer depths to optimize your memory usage.
Before you begin, make sure you understand:
•
the structure of the meter’s logging framework
•
the meter’s existing logging configuration
•
your data logging requirements
Changing your meter’s log configuration deletes all existing records from that log.
NOTICE
DATALOSS
Failure to follow these instructions can result in data loss.
Ensure that all important data is recorded before configuring a log.
The default log settings are designed to meet the needs of most users.
This procedure provides the steps for configuring settings for a subset of data logs using the ION
Setup Assistant. Configuring these settings for custom logs, and logs not listed in the Logging >
Memory screen, is an advanced procedure; see the ION Setup help for more information.