Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 385
DC8-037-2.02, Edition 10.2017
Processing type Parameter Meaning
Sw_Seq_addtl_com Switching sequence: Select the additional
command
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element
QOC>8 If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
RS_Image Parameter works only with ACP 1703 platform
DO_SC_2POL – single
command output 2-pole
Retry_suppression_T Command retry suppression time in seconds.
Within this time a command with same ad-
dress is discarded without error information (s)
0.1 to 6553.5
Output_t Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
select_execute_t Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0.1 to 102.3
Sync_t Within this time (in sec) the interlock enabling
must occur on the command.
0 = no syncronisation over interlocking
0.1 to 6553.5
RS_Mon_t Return state information monitoring time in
seconds (S).
0 = no return state information monitoring
0.01 to 655.35
Command_prolong_t Command prolongation time in seconds (S)
0.01 to 327.67
RS_outp_same_state_1 Selection of command output and command
confirmation, if return state is already end
position before output.
Attention: only active if RS_mon_t is ≠ 0.
Sync_Input_t Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation
input.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
1_out_of_n_t Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5